Blogs & News

Why do Fume Hoods Fail? A Guide to Fume Hood Testing and Maintenance

Fume hoods are essential pieces of equipment in any laboratory or workspace where hazardous materials or chemicals are used. They work by drawing in air from the room and expelling it outside, preventing dangerous fumes and vapors from escaping into the workspace. However, like any piece of equipment, fume hoods can fail over time, which can put users at risk. That’s why regular fume hood testing and maintenance is essential.

What is a fume hood?

A fume hood is a type of ventilation system that is designed to contain and exhaust fumes and vapors generated by laboratory processes. They work by drawing in air from the room, containing the fumes and vapors, and then expelling the air outside. Fume hoods typically have a sliding sash that can be opened or closed to adjust the airflow.

Fume hoods have a sliding sash that can be opened or closed to adjust the airflow, and standard fume hoods typically have face velocities between 80-120 FPM (Feet Per Minute). This range provides the optimum balance between containment and exhaust flow. Fume hoods that exhaust at less than 80 FPM do not adequately contain fumes and vapors, while anything over 120 FPM can cause significant containment problems.

Fume Hood Testing is essential

In order to determine if your fume hood is operating within standard range, regular fume hood testing is essential. At H2I Group, we use the standard SEFA air flow test when testing most fume hoods. This involves measuring the face velocity at the sash plane of the fume hood, but how many sample points taken at the sash is determined by the size and model of your fume hood. These tests are conducted using a hot wire anemometer, which ensures accurate readings of airflow velocity in FPM.

Common reasons fume hoods fail

If your fume hood is not performing at its best, it could be due to various reasons. While replacing the hood might be necessary if it has reached its end of life, there could be other underlying issues. Here are five common reasons why your fume hood might be failing:

1. EXHAUST FAN BELT

The belt that drives the exhaust fan can stretch and slip over time, resulting in a lower face velocity. Belts typically have a life expectancy of 1-2 years and may suffer from stretch and dry rot. 

2. LAB EXHAUST FAN

If the lab exhaust fan has exceeded its life expectancy or hasn’t been properly maintained, it can cause issues. Rusting, deteriorating bearings, pulleys, and belts can lead to decreased performance.

3. Chemicals and Procedures

The hood may have been designed to handle specific chemicals or processes, and changes in these can damage the ductwork and lab exhaust fan, leading to lower face velocity. 

4. Blockage in the Ductwork and Fan

It is very common to find blockages from items like chem wipes and napkins. This can reduce airflow and lower face velocity.

5. Balance Issues

Changes in pressure due to remodeling or new construction can throw off the airflow balance, requiring rebalancing of the system. Airflow can be sensitive and will find the path of least resistance.

How can H2I Group Help?

H2I Group can help identify any issues with your fume hood by testing and certifying your fume hoods. We’ll provide a compliance report for each hood tested, indicating any necessary repairs or replacements. However, any repairs or replacement of materials and parts are excluded from our certification services.

In conclusion, regular fume hood testing and maintenance is essential to ensure that they are functioning properly and keeping users safe. At H2I Group, we can help you with your fume hood testing needs, from the initial design and installation process to testing and certification. Contact us today to learn more about how we can help keep your workspace safe.

recent blogs

Discover how AASPMN, MNCARS, Infento, and H2I Group are shaping the future of automotive education in Minnesota with a $50,000 EV Scholarship Program. This initiative provides schools with hands-on EV kits, teacher training, and resources to prepare students for careers in the evolving automotive industry.
Purchasing the right products for your school or facility can be a complicated, time-intensive process, especially when you’re balancing budgets, timelines, and strict procurement requirements. Cooperative purchasing contracts are designed to make this process easier and more cost-effective.
Pickleball has taken the sports world by storm, becoming one of the fastest-growing recreational activities in the United States. Whether you’re a dedicated player or a facility manager looking to offer a new athletic option, a properly installed pickleball court is essential for a high-quality playing experience.

GET STARTED

LET’S TALK ABOUT YOUR PROJECT TODAY

Are you in need of expert guidance for your building project? H2I Group’s experienced professionals are here to assist you with any questions or concerns you may have. Contact us today to learn more about our services and how we can help you achieve your goals.

CONTACT US

By submitting this form, you agree to receive communications from H2I Group about our products and services.
H2I Group uses uses cookies and similar technologies as strictly necessary to make our site work. We and our partners would also like to set additional cookies to analyze your use of our site, to personalize and enhance your visit to our site and to show you more relevant content and advertising. For more information, please read our Privacy Statement.